Leaving Certificate Physics16.5 Transformers and the transmission of electricity

All books

16.5 Transformers and the transmission of electricity — Practise with help

Warm-up: remember

  1. A resistor of resistance 5.0 Ω carries a current of 3.0 A. Calculate the power transferred to it.
  2. What kind of supply must a transformer be connected to?
Answers and feedback
  1. P=I2R=3.02×5.0=9.0×5.0=45 WP = I^2R = 3.0^2 \times 5.0 = 9.0 \times 5.0 = 45\,\text{W}. This is the equation that explains the waste in a transmission cable.
  2. An alternating supply. A steady direct current makes a steady flux, and a steady flux induces no emf in the secondary coil.

Practise with help

1. A transformer has 200 turns on the primary and 800 turns on the secondary. The primary voltage is 12 V. Calculate the secondary voltage.

Hint

Use VsVp=NsNp\dfrac{V_s}{V_p} = \dfrac{N_s}{N_p}.

Next step

Vs=12×800200V_s = 12 \times \dfrac{800}{200}.

Full working Vs=Vp×NsNp=12×800200=12×4=48 VV_s = V_p \times \frac{N_s}{N_p} = 12 \times \frac{800}{200} = 12 \times 4 = 48\,\text{V}

The secondary has more turns than the primary, so the voltage is stepped up.

2. A transformer has 1000 turns on the primary and 100 turns on the secondary. The primary voltage is 230 V. Calculate the secondary voltage.

Hint

The ratio of the turns is now less than one.

Next step

Vs=230×1001000V_s = 230 \times \dfrac{100}{1000}.

Full working Vs=Vp×NsNp=230×1001000=230×0.10=23 VV_s = V_p \times \frac{N_s}{N_p} = 230 \times \frac{100}{1000} = 230 \times 0.10 = 23\,\text{V}

This is a step-down transformer. The secondary voltage is ten times smaller than the primary voltage, because it has one tenth of the turns.

3. A transformer steps a voltage of 240 V down to 12 V. The primary coil has 500 turns. Calculate the number of turns on the secondary.

Hint

Rearrange the transformer equation for NsN_s.

Next step

Ns=Np×VsVp=500×12240N_s = N_p \times \dfrac{V_s}{V_p} = 500 \times \dfrac{12}{240}.

Full working Ns=Np×VsVp=500×12240=500×0.050=25N_s = N_p \times \frac{V_s}{V_p} = 500 \times \frac{12}{240} = 500 \times 0.050 = 25

The secondary coil has 25 turns. Fewer turns give a smaller voltage.

4. An ideal transformer has a primary voltage of 12 V and a primary current of 2.0 A. The secondary voltage is 48 V. Calculate the secondary current.

Hint

An ideal transformer transfers all the power, so VpIp=VsIsV_pI_p = V_sI_s.

Next step

Is=VpIpVs=12×2.048I_s = \dfrac{V_pI_p}{V_s} = \dfrac{12 \times 2.0}{48}.

Full working Is=VpIpVs=12×2.048=2448=0.50 AI_s = \frac{V_pI_p}{V_s} = \frac{12 \times 2.0}{48} = \frac{24}{48} = 0.50\,\text{A}

The power is 24 W on both sides: 12×2.0=2412 \times 2.0 = 24 W and 48×0.50=2448 \times 0.50 = 24 W. The voltage went up four times, so the current went down four times.

5. A transformer has an input power of 800 W and an output power of 720 W. Calculate its efficiency.

Hint

Efficiency is the output power divided by the input power, as a percentage.

Next step

efficiency=720800×100%\text{efficiency} = \dfrac{720}{800} \times 100\%.

Full working efficiency=720800×100%=90%\text{efficiency} = \frac{720}{800} \times 100\% = 90\%

The missing 80 W is transferred to the core and the windings of the transformer, which warm up a little.

6. A power station delivers 10 kW along a cable of resistance 5.0 Ω. Calculate the power lost in the cable when the transmission voltage is 10 kV. Then calculate the power lost when the same power is sent at 500 V, and compare the two answers.

Hint

Find the current first, using I=PVI = \dfrac{P}{V}. Then use Plost=I2RP_{\text{lost}} = I^2R.

Next step

At 10 kV, I=10 00010 000=1.0I = \dfrac{10\,000}{10\,000} = 1.0 A. At 500 V, I=10 000500=20I = \dfrac{10\,000}{500} = 20 A.

Full working

At 10 kV:

I=PV=10 00010 000=1.0 AI = \frac{P}{V} = \frac{10\,000}{10\,000} = 1.0\,\text{A} Plost=I2R=1.02×5.0=5.0 WP_{\text{lost}} = I^2R = 1.0^2 \times 5.0 = 5.0\,\text{W}

At 500 V:

I=10 000500=20 AI = \frac{10\,000}{500} = 20\,\text{A} Plost=I2R=202×5.0=400×5.0=2000 WP_{\text{lost}} = I^2R = 20^2 \times 5.0 = 400 \times 5.0 = 2000\,\text{W}

At 500 V the cable wastes 2000 W, which is 2.0 kW out of the 10 kW sent. At 10 kV it wastes only 5.0 W. The current is 20 times smaller, and the loss depends on the square of the current, so the waste falls by a factor of 400.

A question from Chapter 14

7. A 24 kW supply delivers its power at 240 V. Calculate the current.

Hint

Use P=VIP = VI.

Next step

I=PV=24 000240I = \dfrac{P}{V} = \dfrac{24\,000}{240}.

Full working I=PV=24 000240=100 AI = \frac{P}{V} = \frac{24\,000}{240} = 100\,\text{A}

A current of 100 A needs a very thick cable and wastes a lot of energy in it. This is exactly why the grid raises the voltage first: the same power at 24 kV needs a current of only 1.0 A.